Yancheng Gold Bull Generator Manufacturing Co., Ltd.

Products Catalog

AMF Control Panel

Home » Products Catalog » AMF Control Panel

AMF Control Panel

 

1. PUSH BUTTONS

PUSH BUTTONS

2. STATUS/MEASUREMENT UNITS

STATUS/MEASUREMENT UNITS

3. ALARM INDICATIONS

ALARM INDICATIONS

21-Oin pressure sensor input 0-Not used
1-VDO 0-5bar
2-VDO 0-10bar
3-Daton 5bar
4-Daton 10bar
5-Daton 7bar
6-Murphy 7bar
7-User configured
22-Coolant temp sensor input 0-Not used
1-VDO 40ºC-120ºC
2-Datcon High
3-Datcon Low
4-Murphy
5-Cummins
6-User configured
23-Oin pressure display input 0-Bar/PSI
1-kPa
24-Preheat/E.T.S hold/ldle 0-Preheat [NOTE 6]
1-E.T.S.hold [NOTE 6]
2-ldle [NOTE 6]
25-Oin pressure switch input 0-Delayed, shutdown, close to activate
1-Delayed, shutdown, open to activate

NOTE:
1. Parameter settings incremental, step by decreasing the effective range of different size. Increased flexibility in the use of settings, regressive step.
2. Flywheel teeth set to zero (0) to disable speed sensor. Collecting only AC motor output frequency, speed value is calculated from the frequency value. ldle units in the following if not power, speed sensor to be connected properly and correctly set flywheel teeth.
3. Low-frequency, voltage limit, in other words, low frequency, undervoltage alamn in the manual invalid address manually ldle activated manually ldle parking.
4. 5, 8, respectively corresponding to the options Options 24 settings.
5. No.11 feet input module to low effective, its use will be left vacant.No.12 feet low input can be high, set up to the first 25.
6. No.24 choice preheating and idling output, the module output pin on the 4th for the fuel solenoild valve control; No.24 choice parking output, the output module for landing and taking off on the 4th-speed control, mainly used in domestic models with stepper motor and the use of limit switches.
7. City monitoring, fault signals can be input to the remote start module inputs. Its effective, if the module works in Zidongdang will automatically activate the unit, automatic load transfer output signal; if module is a manual operation, the output load transfer signals.
8. Overcument protection against single-phase, three-phase, not only from all over-cument protection. Overcurrent protection for the exchange value of the actual movements change current transformer and overcurrent protection than the percentage of plot to default values for example, overcument protection action when cument value I=500*110%=550(A).

4. OPERATION

1. MANUAL OPERATION:
Press the first, then press the pushbutton, When the controller is in the manual mode (indicated by an LED indicator beside the button), pressing the START(I) button will initiate the start sequence.
Selecting STOP(O) de-energises the FUEL SOLENOID, bringing the generator to a stop.

2. AUTOMATIC MODE OF OPERATION
Press the first, then press the button, When a Remote Start signal is appiled to the remote start input, the following sequence is initiated.
On removal of the Remote Start signal, the stop delay timer is initiated, once it has timed out, the load Transfer signal is de-energised, removing the load. The Cooling timer is then initiated, allowing the engine a cooling down period off load before shutting down. Once the Cooling timer expires the Fuel Solenoid is de-energised, bringing the generator to a stop.

3. MANUAL MODE Transfer AUTOMATIC MODE
When the controller is in the manual mode and the engine is running, press the pushbutton, generator will goto the AUTOMATIC MODE.

4. CLEAR THE FAULT
Press the button, clear the fault and goto the STOP MODE.

5. GIVE(CUT0) ALOAD TRANSFER SIGNAL IN THE MANUAL MODE
When the Remote Start signal is invalid, Press the button and + button simultaneously, the load transfersignal will be effective.

6. CORRECT THE ERROR OF THE AC VOL TAGE
If the Generator rated voltage is 400V, then the parameter of the 20th will be set at 400. Working the generator and do not any load, adjust the AVR controller to make the AC voltage of generator is 400V, Press the button and button simult aneously. Correct the error AC voltage is finished, When the Common alarm LED Was flashing.

5. ACCESSING THE CONFIGURATION EDITOR

Press the info and Stop/Reset button simultaneously. The LED beside the AUTO button will flash continuously to indicate that configuration mode has been entered. The first configuration setting is displayed.

6. EDITING THE PARAMETER

Enter the editor as descnibed above . Press to enter edit mode. The symbol will flash on the display to indicate that edit mode has been entered. Press +/- to change the parameter to the desired value. Press to save the value and exit edit mode for this parameter. The symbol will be removed from the display to indicate that edit mode has been exited. To select value to edit, press the +/- buttons. Continuing to press the + and - buttons will cycle through the adjustable parameters as shown in the following lists. NOTE:To exit the front panel configuration editor at any time, press the Stop/Reset button.

7. PARAMETER DESCRIPTOR LIST
0 - Start delay 0-240s(5s)
1 - Over current percent 50-200%(200%) [NOTE 8]
2 - Crank attemput 3-60s(10s)
3 - Crank rest 3-60s(10s)
4 - Safety delay 8-60s(8s)
5 - Warming up/Speed up(down)/Speed up 0-60m(10s) [NOTE 4]
6 - Return delay 0-60m(30s)
7 - Coolant down time 0-60m(60s)
8 - Preheat/E.T.S.hold/ldle 0-240s(5s) [NOTE 8]
9 - Sensor fail 1-5s(4s)
10 - Fail to Stop 10-60s(60s)
11 - Low Oil Press. 5-150PSI(15PSI)
12 - High Temp 50-150ºC(95ºC)
13 - Generator low voltage 50-380V(10V)
14 - Generator high voltage 200-500V(450V)
15 - Under Frequency (Speed) 0-60Hz(40Hz)/0-1800RPM(1200RPM)
16 - Over Frequency (Speed) 50-72Hz(57Hz)/1500-2160RPM(1710RPM)
17 - Charge Alt Failure 0.0-24.0VDC(8.0VDC)
18 - Flywheel teeth 0-240(0) [NOTE 2]
19 - CT Rrimary 10-6000A/5A(500A/5A)
20 - Generator rated voltage 100-700V(400V)